Imagen
ADS Outalarm® with Capacitance Probe

A100HC48A - Alarma A100 Outalarm® con Sonda de Capacitancia Alta Temperatura

Dixon Distributor? 

Log in to view pricing, inventory, place orders & much more. If you want to create an account, please click the button to begin the registration process.

Atributos

Peso
3,5 lb
Break Quantity
0
Paquete Opcional/Cantidad por Caja
0
Rango de Temperatura
Packing: Rubber°F (Please specify oxygen user when ordering, Super Swivels® are not recommended for breathing air or steam°C)
Longitud
Seat: red natural rubber"
Valor de Presión
50 PSI, consulte Dixon para aplicaciones mayores a 300 PSI

Detalles

Applications

Specifically designed for liquid terminal operation on batch loading and overfill protection, unloading, tank cars, tank trucks, marine barges, suitable for open and close dome

Available Options

24", 36", 48" and 60" probe lengths standard, other lengths available

Construction

Wetted materials: 316 stainless steel, PTFE standard, other materials available

Features

  • Totally self-contained; no wires, tubing or external power
  • Rugged weather and corrosion resistant construction
  • No moving parts, tip sensitive phase shift™ digital capacitance sensor for conductive and non-conductive fluid
  • Requires no calibration or adjustment
  • Adjustable insertion length through a standard 1/2" NPT fitting
  • High intensity audible and flashing visual outputs
  • Optional opto-isolated solid state contact output
  • Full, hard graduated laser engraved rod
  • A100 funciona hasta 2500 horas con una sola batería alcalina de 9 V
  • Fail safe continuous battery monitor goes to alarm state on low battery
  • Battery current drain 0.23 ma during standby; 50 ma in alarm state

Specifications

  • Intrinsically safe design per ANSI/UL913 Class I, Div I Groups A, B, C and D Hazardous Areas
  • Minimum dielectric constant 1.7
  • Temperature range: high-temp capacitance probe: -14°F to 325°F (-26°C to 163°C)
  • Activation point 1/4" into the liquid
  • Compatible with any liquid or dry bulk material with a dielectric constant of 1.7 or greater
  • Horn intensity 101 dB at 2'
  • Light output 3 each 3000 mcd high intensity flashing LED's
  • Pressure rating on standard unit: 50 PSI, consult Dixon® for applications up to 300 PSI

Recursos