877-963-4966

Double Clapper Siamese Connection Back Outlet

Double Clapper Siamese Connection Back Outlet

×
Part Number DCS4030F
Branding Auto-Sprinkler
Material Cast Brass
Inlet (2) 3" female NST (NH)
Outlet 4" female NPT
Maximum Operating Pressure 175 PSI
Optional Pkg/Box Qty 1
Weight Lb 20.8000

Applications

  • Provides the required 500 GPM minimum to supplement the fire protection as an auxiliary inlet connection to the water supply. (250 GPM minimum per inlet.)

Specifications

  • Factory Mutual approved

Features

  • Exposed Fire Department Connections (FDC) provide an economical method of satisfying local fire codes.

×

Catalog Page

×

Related Products

×
×
×
×
×